Specifications: Fluke 353 True RMS 2000 A Clamp Meter
| Electrical Specifications | ||||
| Current measurement DC and AC 10 Hz to 100 Hz | Range | 40 A / 400 A / 2000 A / 1400 AC RMS | ||
| Resolution | 10 mA / 100 mA / 1 A | |||
| Accuracy | A: 1.5% rdg + 15 digits A: 1.5% rdg + 5 digits | |||
| Trigger level for Inrush | 0.50 A / 5.0 A / 5 A | |||
| Trigger level for Hz filter OFF | 2.50 A / 2.5 A / 8 A | |||
| Trigger level for Hz filter ON | 0.50 A / 2.5 A / 8 A | |||
| Crest Factor (50/60 Hz) | Range | 40 A / 400 A / 2000 A / 1400 AC RMS | ||
| Crest Factor1 | 2 @ 33 A, 2.4 @ 27 A 2 @ 330 A, 2.4 @ 270 A 2 @ 1000 A, 2.4 @ 833 A | |||
| Current measurement AC 100.1 Hz to 1 kHz | Range | 40 A / 400 A / 2000 A; 1400 AC RMS | ||
| Resolution | 10 mA / 100 mA / 1 A | |||
| Accuracy | 10 A: 3.5% rdg + 15 digits 10 A: 3.5% rdg + 5 digits | |||
| Trigger level for Inrush | 0.50 A / 5.0 A / 5 A | |||
| Trigger level for Hz filter OFF | 2.50 A / 2.5 A / 8 A | |||
| Trigger level for Hz filter ON | 0.50 A / 2.5 A / 8 A | |||
| Frequency measurement | Measurement range | 5.0 Hz to 1 kHz | ||
| Resolution | 0.1 Hz (15 Hz to 399.9 Hz); 1 Hz (400 Hz to 1 kHz) | |||
| Accuracy – 5.0 Hz to 100 Hz | 0.2% + 2 counts | |||
| Accuracy – 100.1 Hz to 1 kHz | 0.5% + 5 counts | |||
| Trigger level | Refer to current and voltage tables | |||
| 1. Add 2% to error spec for CF > 2 | ||||
| General Specifications | ||||
| Batteries | Six 1.5 V AA NEDA 15 A or IEC LR6 | |||
| Battery life (with typical usage, backlight off) | 100 hours | |||
| Test leads | Rated to 1000 V | |||
| Weight | .814 kg (1.8 lb) | |||
| Jaw size | 58 mm (2.28 in) | |||
| Dimensions (L x W x D) | 300 x 98 x 52 mm (12 x 3.75 x 2 in) | |||
| Safety rating | IEC 61010-2-032, 600 V CAT IV, 1000 V CAT III | |||
| Environmental Specifications | ||||
| Operating temperature | 32°F to +122°F (0°C to +50°C) | |||
| Storage temperature | -4°F to 140°F (-20°C to +60°C) | |||
| Operating humidity | 0 to 95% (non-condensing) | |||
| Operating altitude | 2000 m | |||
| Storage altitude | 10,000 m | |||
| IP rating | 42 (indoor use only) | |||
| Drop test requirements | 1 m | |||
| EMI, RFI, EMC | FCC part 15, IEC/EN 61326-1:1997 class B IEC/EN 61326:1997 3V/m, performance criteria B, EN61325 | |||
| Temperature coefficients | Current | 0.1% of reading per °C outside 22°C to 24°C | ||
| Voltage | 0.1% of reading per °C outside 22°C to 24°C | |||